Air Changes per Hour Calculator
Convert room airflow and volume to ACH, or estimate whole-dwelling outdoor air with the ASHRAE 62.2 and IRC formulas.
ACH from a fan is only as good as the CFM you entered. The ventilation rates are the published ASHRAE 62.2 and IRC-style formulas, before any local amendment or infiltration credit.
Air changes per hour
5.00
2,400 ft³ of room.
Formula with your numbers
ACH = (200 CFM × 60) / (20 × 15 × 8) = 5.00
This is a turnover of whatever air the CFM describes. Outdoor-air ventilation and recirculated supply air are different jobs.
How this estimate works
Air changes per hour is a rate, not a fan model. If a room has a known airflow in cubic feet per minute and a known volume in cubic feet, ACH = (CFM × 60) / volume. The 60 turns minutes into an hour. Reverse it and CFM = (ACH × volume) / 60. Both directions are on this page. A 20 by 15 foot room with an 8 foot ceiling has 2,400 cubic feet. At 200 CFM that room turns over (200 × 60) / 2,400 = 5 ACH. None of that tells you whether the air is outdoor air or air the system is recirculating. You have to know which fan you measured.
Those two meanings get mixed up constantly. Ventilation ACH is outdoor air brought in to dilute odors, moisture, and pollutants. Supply-air turnover is the conditioned air the blower is moving, most of which was already inside the house. A comfortable cooling system often moves several air changes per hour of supply air. Doing the same thing with outdoor air would throw the heating and cooling bill away. If you are checking a supply register, you are in the second category. If you are checking a fresh-air fan or an ERV, you are in the first.
Whole-dwelling outdoor air has a published formula, and this page shows two versions. ANSI/ASHRAE Standard 62.2, from the 2013 edition onward, sets Qtot = 0.03 × floor area + 7.5 × (bedrooms + 1), in CFM. Bedroom count is not taken below one, so a studio is treated as two people. That rate is the total before any blower-door infiltration credit. A fan that runs only part time must be larger while it is on. This tool skips the leakage credit and assumes continuous operation.
Many adoptions of the International Residential Code use a lower floor-area term, 0.01 × area, with the same 7.5 CFM per assumed person. A 2,000 square foot, three-bedroom house is 90 CFM under the ASHRAE equation (0.03 × 2,000 + 7.5 × 4) and 50 CFM under the IRC-style equation (0.01 × 2,000 + 30). The page shows both so you can see the gap. The number that matters is the one in the code edition your state or city actually adopted, including local amendments. Bathroom and kitchen exhaust are separate. A long-standing IRC local-exhaust screen is 50 CFM intermittent or 20 CFM continuous for a bathroom, and 100 CFM intermittent or 25 CFM continuous for a kitchen. Confirm the edition before you buy a fan.
An older rule of thumb said a house should have about 0.35 natural air changes per hour. That figure is not the current 62.2 procedure, and it is a poor substitute for the floor-area-plus-people equation. It is listed here so you can recognize it, not so you can design to it. Supply-air turnover is a different illustration: a house with eight-foot ceilings, 400 CFM per ton, and one ton per 500 square feet moves (400 × 60) / (500 × 8) = 6 ACH of supply air. That example is derived from those assumptions. It is not a target you have to hit in every room.
If you have a measured CFM and want a duct, use the duct size calculator. If you have tons or a sensible BTU load and need CFM, use the CFM calculator, then come back here if you want that airflow expressed as ACH. Neither page replaces a blower-door test. A blower door measures leakage under a set pressure. This formula only converts a flow you already know into air changes.
Questions homeowners ask
Is a higher air-change rate always better?
No. More outdoor air improves dilution and raises the heating and cooling load. More supply air can help mixing, but too much airflow is noisy and can hurt dehumidification. Match the rate to the job: ventilation, or conditioning, not a single bigger-is-better number.
How is this different from the CFM calculator?
This page is the relationship between airflow and room volume. The CFM calculator also estimates airflow from equipment tons and from sensible heat. Use this page when you already have CFM, or when you are checking a ventilation standard. Use the CFM page when you are starting from tons or BTU.
Why does the page show two ventilation rates?
ASHRAE 62.2 uses 0.03 CFM per square foot plus 7.5 CFM per assumed person. Recent IRC whole-dwelling formulas use 0.01 CFM per square foot with the same people term. They are different published rules. Your local code decides which one applies.
Does the old 0.35 ACH rule still apply?
It is an older whole-house rule of thumb, not the current ASHRAE 62.2 equation. Houses are tighter than they were when that figure was common. Use the floor-area and bedroom formula, then apply any infiltration credit your code actually allows from a blower-door test.
Can I measure air changes with this calculator?
You can convert a known CFM into ACH. Getting that CFM takes a flow hood, a calibrated fan, or the equipment’s measured airflow. A blower-door number is infiltration under pressure, which is a different test and is not what this formula computes.