Duct Size Calculator
Find a round metal duct diameter from airflow and friction rate, then check velocity and a few rectangular equivalents.
Diameter comes from a friction-chart fit for smooth round metal duct. It is not an ACCA Manual D layout, and it is not a flexible-duct size.
Inches of water per 100 feet. 0.08 is a common residential starting assumption, not a measurement.
Used only to judge velocity. It does not change the diameter.
Round metal size
12 in
Chart diameter 10.27 inches, rounded up to the next standard size.
Velocity at that size
509 fpm
Inside the 500–700 fpm screen for a supply branch.
Rectangular equivalents
- 12 × 10 in, equivalent round 12.0 in
- 16 × 8 in, equivalent round 12.2 in
- 22 × 6 in, equivalent round 12.0 in
Formula with your numbers
Diameter = (0.109136 × 400^1.9 / 0.08) ^ (1 / 5.02) = 10.27 in Velocity = 400 / (π × (12 / 24)²) = 509 fpm
Smooth round metal only. Flexible duct needs the manufacturer’s friction data and is usually larger.
How this estimate works
Duct size on this page is the round metal diameter that carries a CFM at a friction rate you choose. The relationship is a power-law fit of the ASHRAE friction chart for smooth galvanized duct at standard air: friction loss in inches of water per 100 feet is about 0.109136 × CFM^1.9 / diameter^5.02, with diameter in inches. The calculator solves that fit for diameter, then rounds up to the next common size from 4 inches through 24 inches. Rounding up matters. A diameter that is a fraction short of the chart will spend slightly more static pressure than you budgeted.
Friction rate is not a property of the room. It is how much pressure loss you are willing to spend per 100 feet of equivalent duct length. A common residential starting assumption is 0.08 to 0.10 inches of water per 100 feet, and 0.08 is the default here. The real budget comes from Manual D: available blower static pressure, minus the pressure the coil, filter, registers, and other devices already use, spread over the longest equivalent run. If you do not know that budget, leave 0.08 and treat the diameter as a screen. Changing the friction rate in the form shows you how sensitive the answer is.
Velocity is CFM divided by the inside area of the round duct. Area in square feet is π × (diameter / 24)^2, because the radius in feet is the diameter in inches divided by 24. The page checks that velocity against ranges many residential designers use: about 700 to 900 feet per minute for a supply trunk, 500 to 700 for a supply branch, 500 to 700 for a return trunk, and 400 to 600 for a return branch. Those are comfort and noise ranges, not a code maximum. A velocity under the range is quiet and may be a larger duct than you need. A velocity over the range is the one to fix, usually by stepping up a size or by moving less air on that run.
Rectangular sizes use the Huebner approximation for equivalent round diameter: 1.30 × (width × height)^0.625 / (width + height)^0.25, dimensions in inches. The three options are small sheet-metal pairs whose equivalent diameter is at least the round size already chosen, with the long side no more than four times the short side. Equivalent diameter is a friction comparison. It does not mean a flat 8×20 duct will be as quiet as a round duct of the same equivalent, because the flat shape can be noisier and harder to fit.
Do not read this diameter as a flexible duct size. Flex has a higher pressure drop than smooth metal, and a sagging run is worse than a straight one. The chart fit is for smooth round metal. Keep flex short, pull it tight, support it, and size a long flex run from the manufacturer’s own friction data, which will usually call for a larger diameter than this page shows. A crushed flex section is a restriction no diameter formula will repair.
You need a CFM before this page is useful. The CFM calculator can produce one from tons, from sensible heat, or from an air-change target. The air-changes page is the place to turn a room volume into that target. None of the three is a Manual D design. Manual D lays out every branch, the equivalent length of every fitting, and the available static pressure of the actual blower. Bring this diameter to that design as a check, not as the design.
| Role | Common low | Common high |
|---|---|---|
| Supply trunk | 700 | 900 |
| Supply branch | 500 | 700 |
| Return trunk | 500 | 700 |
| Return branch | 400 | 600 |
Questions homeowners ask
Is this a Manual D duct design?
No. Manual D starts from the blower’s available static pressure, subtracts the devices, and sizes every run for the room CFM from the load calculation. This page solves one friction-chart equation for one airflow. It is a screen you can audit, not a duct layout.
What friction rate should I enter?
If you do not have a Manual D friction rate, 0.08 inches of water per 100 feet is a common residential starting assumption. The real rate depends on how much static pressure is left after the coil, filter, and grilles, and on how long the equivalent run is. Move the input and watch the diameter change.
Why is the velocity outside the suggested range?
Rounding up to a standard diameter lowers velocity. A high velocity means the duct is small for that CFM and will be noisier and use more pressure. Step up a size or reduce the airflow on that run. A low velocity is usually acceptable; it just may be more metal than a tight design would use.
Can I order flexible duct at this diameter?
Not as a direct substitution. The formula is for smooth round metal. Flexible duct, especially if it sags or takes a tight bend, loses more pressure. Size long flex runs from the duct manufacturer’s friction data and keep the runs short.
Should I use round or rectangular duct?
Round metal is the shape the friction fit describes, and it is usually quieter for the same airflow. The rectangular options are equivalents when a joist bay or a chase will not take the round size. Stay away from very flat rectangles; the page limits the long side to four times the short side.
Related calculators
- CFMCFMEstimate airflow from tons, from sensible heat and temperature difference, or from a target air-change rate.
- ACHAir changes per hourConvert room airflow and volume to ACH, or estimate whole-dwelling outdoor air with the ASHRAE 62.2 and IRC formulas.