Mini-Split BTU Calculator

Estimate mini-split BTU/h for each room, then match a standard nameplate from 6,000 to 36,000. A screening size, not a Manual J.

Room screens use the same climate factors as the whole-house heat pump tool, plus a 4,000 BTU/h kitchen allowance on cooling. This is not a Manual J.

Room 1
ft²
ft

Outdoor connected capacity

9,000 BTU/h

Sum of the indoor nameplates. No diversity credit is applied.

  • Primary bedroom

    Screen 8,000 BTU/h (heating). Suggested head 9,000 BTU/h, 13% above the screen.

Formula

Cooling BTU/h = area × (12,000 / ft² per ton) × insulation × (ceiling / 8) × glass + kitchen adder Heating BTU/h = area × heating BTU/ft² × insulation × (ceiling / 8) Head = smallest catalog size at or above the larger of those two. Primary bedroom: cooling 5,455 = 5,455; heating 8,000

How this estimate works

A ductless mini-split is sized room by room. Each indoor unit has a nameplate in BTU per hour, and the common catalog steps are 6,000, 9,000, 12,000, 15,000, 18,000, 24,000, 30,000, and 36,000. This calculator estimates a heating screen and a cooling screen for each room with the same climate factors as the whole-house heat pump tool, then picks the smallest standard nameplate that covers the larger of the two. The outdoor unit’s connected capacity is the sum of those nameplates.

The room screen starts from floor area, climate, insulation, ceiling height, and glass. A kitchen gets an extra 4,000 BTU/h on the cooling side only. That adder shows up on many manufacturer worksheets as an allowance for cooking, and it is an allowance, not a measured range. A sunroom is treated as large-glass even if you marked the windows as typical, because the glass is the load. Heating does not get the kitchen adder and does not get the glass penalty. Sun through the glass reduces the heating load; counting it as extra heat loss would oversize the head for winter.

Inverter heads can turn down, which is why a small mismatch is less punishing than it is with a single-stage central system. They cannot turn down to zero. The lowest continuous speed still has to match the room if you care about humidity. When the recommended nameplate is more than about 25 percent above the screen, the result says so. A small bedroom often lands on a 6,000 BTU/h head because that is the smallest common size, even when the screen is well below 6,000. That is a catalog limit, not a sign that the room needs 6,000 BTU/h. Ask the installer for the minimum capacity, not only the nameplate.

For several rooms, add the selected indoor nameplates to see the connected capacity the outdoor unit has to support. This tool does not take a diversity credit. Diversity is the idea that the kitchen and the bedrooms will not all peak at the same hour, so the outdoor unit can be smaller than the sum. Sometimes that is reasonable, and sometimes every room peaks together on the same afternoon. Leaving the credit off keeps the screen conservative. A contractor who applies diversity should show you which rooms they assumed would not coincide.

A room whose screen is above 36,000 BTU/h does not get a fake head size. That is a large open area, and it usually wants two indoor units or a ducted system so the air actually reaches the far side of the room. One oversized head in a corner leaves a stagnant zone. Placement, line-set length, and the outdoor unit’s capacity at the winter design temperature matter as much as the nameplate. Those are site conditions this page cannot see.

Use the result as the agenda for the quote: which rooms, which head size, and whether the outdoor unit is being asked to heat on a cold morning. The whole-house heat pump calculator is the companion if you are comparing a ducted system. The CFM calculator is the companion if you are checking airflow against a sensible load. The replacement cost calculator turns a zone count into a planning range and is where you can request quotes from contractors.

Screening factors used by the heat pump and mini-split calculators
ClimateWhere it roughly fitsft² per cooling tonHeating BTU/h per ft²
Hot-humidGulf Coast, Florida, Hawaii45020
Hot-dryDesert Southwest40025
MixedMid-Atlantic, upper South, southern Midwest55032
ColdNortheast, Upper Midwest, Mountain West65045
Very coldNorthern Plains, northern New England, Alaska75058
Insulation, glass, and what they multiply
InputFactorMeaning
Insulation: Poor1.18Little insulation, original single-pane windows, noticeable drafts
Insulation: Average1Some attic insulation and mixed windows, typical of many 1980s–2000s houses
Insulation: Good0.86Attic and walls near current code, double-pane windows
Insulation: Excellent0.75Deep retrofit or a new high-performance envelope
Glass: Shaded or few windows0.95Applied to cooling only
Glass: Typical window area1Applied to cooling only
Glass: Large or west-facing glass1.12Applied to cooling only
Ducts inside conditioned space1.00 / 1.00Cooling factor / heating factor
Ducts in an attic or crawlspace1.15 / 1.10Flat uplift, not a measured duct loss
Ductless1.00 / 1.00No duct uplift
Ceiling heightheight / 8Eight feet is the baseline the rules of thumb assume

How the mini-split BTU result is chosen

A ductless head is sold by BTU per hour. One ton is 12,000 BTU/h. This page estimates a cooling screen and a heating screen for each room, then selects the smallest common nameplate that covers the larger of the two: 6,000, 9,000, 12,000, 15,000, 18,000, 24,000, 30,000, or 36,000. A screen of about 10,000 BTU/h becomes a 12,000 BTU/h head. That step is a catalog size, not extra load you measured.

The number is a screening estimate, not a Manual J and not a certified BTU. It does not count each wall or the direction of each window. Use it to see whether a bedroom is in the 6,000 or 9,000 range, and whether a large room needs two heads. For a planning range on the installed cost, the AC replacement cost calculator has a ductless band you can edit. That range is not a quote, and it does not list installers near you. A whole-house ducted comparison starts on the heat pump size calculator.

Request local quotes

Name, ZIP, and a phone or email. This does not reserve a price.

Enter a phone number, an email, or both.

Questions homeowners ask

Why not one large mini-split for the whole house?

One head conditions the room it can throw air into. Closed bedrooms and a far living room will not share that air reliably. Multi-zone systems, or a ducted air handler, exist because distribution matters as much as total BTU.

What if the recommended size is much larger than the BTU estimate?

The tool steps up to the next catalog size that covers the screen. If that jump is large, it is flagged. A modulating unit can run below its nameplate, but its minimum capacity still has to suit the room. For a small bedroom, a 6,000 BTU/h head is often the smallest unit sold, even when the screen is lower.

How should the outdoor unit be sized for several rooms?

This page sums the indoor nameplates and does not apply a diversity factor. That connected total is the conservative screen. A contractor may select a smaller outdoor unit when the rooms will not peak together, and should say which rooms they left out of the peak.

Do mini-splits still need a load calculation?

Yes. Room area and a climate factor are a screen. Manual J still counts the actual walls, windows, and infiltration, and Manual S still governs how the equipment is selected against that load. Line-set length and low-ambient capacity are part of that selection.

Can I size a garage with this?

Not well. A garage is often uninsulated, leaky, and only heated occasionally, and it may be separated from the house for fumes. The factors here are for living space. A garage heater or a dedicated mini-split needs its own look at insulation and use.

How many BTU does a mini-split need?

Use the room screen on this page, in BTU per hour, and take the smallest standard nameplate at or above it. One ton is 12,000 BTU/h. A screen under 6,000 BTU/h still lands on a 6,000 BTU/h head because that is a common smallest size. Above 36,000 BTU/h, one head is a poor way to cover the room. This is not a Manual J and it does not certify the BTU.