CFM Calculator

Estimate airflow from tons, from sensible heat and temperature difference, or from a target air-change rate.

400 CFM per ton and the 1.08 sensible-heat factor are sea-level screening equations. They are not a measurement of your blower.

Start from
tons
CFM

400 is the usual starting point. The common band is 350 to 450.

Equipment airflow

1,200 CFM

Check this against the blower table at the duct system’s external static pressure.

Formula with your numbers

CFM = 3 tons × 400 CFM/ton = 1,200

How this estimate works

CFM is cubic feet per minute, the airflow number ducts, blowers, and ventilation fans are actually selected with. This page offers three standard ways to estimate it. They answer different questions, so the labels stay on the result. Tons tell you a rule-of-thumb equipment airflow. Sensible heat and a temperature difference tell you the airflow that carries a known BTU load. Room volume and a target air-change rate tell you the airflow that produces that rate. None of them measures the fan you already own.

The equipment rule is CFM = tons × CFM per ton, with 400 as the default. The usual published band is about 350 to 450 CFM per ton of cooling. It lines up with a coil temperature drop near 15 to 20°F at typical indoor conditions. Lower airflow runs the coil colder and can pull more moisture, until it is low enough to risk freezing. Higher airflow moves more sensible heat and less latent heat. The input is yours to edit inside that band. A 3-ton system at 400 CFM per ton is 1,200 CFM. That is the blower target people mean when they say “400 a ton,” and it still has to be checked against the manufacturer’s fan table at the external static pressure of the duct system.

The heat equation is BTU/h = 1.08 × CFM × ΔT, solved for CFM. The 1.08 is standard air at sea level: about 0.075 pounds per cubic foot, times about 0.24 BTU per pound per degree, times 60 minutes per hour. ΔT is the temperature difference between the supply air and the room air, not the thermostat setpoint by itself. For cooling, 18°F to 20°F is a common design difference. A heat pump in heating often has a smaller rise, sometimes 15°F to 30°F. A gas furnace rise is larger, often somewhere in the 35°F to 65°F range on the nameplate, and you should use the rise the furnace is designed for rather than a cooling number. If you enter 12,000 BTU/h of sensible load and a 20°F difference, CFM = 12,000 / (1.08 × 20), about 556 CFM.

Sea level is built into the 1.08 factor. Air at elevation is less dense, so the same BTU needs more CFM. In mountain towns the gap is often on the order of 10 to 20 percent. This tool does not apply that correction. Above a few thousand feet, treat the sensible-heat CFM as a low estimate.

The third mode is the air-change formula, CFM = ACH × length × width × height / 60. It matches the air-changes calculator in the other direction. Use a ventilation ACH, such as a number well under 1, only when you mean outdoor air. Use a higher ACH only when you mean supply air being recirculated. Mixing those up is how a fresh-air fan gets specified like a cooling blower. A worked supply-air illustration lives on the air-changes page: eight-foot ceilings, 400 CFM per ton, and one ton per 500 square feet come out to about 6 ACH.

Once you have CFM, the duct calculator can turn it into a round diameter. The heat pump calculator is where tonnage gets its screen. Sensible load changes temperature. Latent load is moisture, and the 1.08 equation ignores it. Feeding total BTU into that equation overstates CFM when part of the load is latent.

Request local quotes

Name, ZIP, and a phone or email. This does not reserve a price.

Enter a phone number, an email, or both.

Questions homeowners ask

Is 400 CFM per ton a requirement?

It is a rule of thumb inside a band of about 350 to 450 CFM per ton, tied to a typical cooling temperature drop. The manufacturer’s fan data at your duct static pressure is the number the blower can actually deliver. Use 400 to start the conversation, then check the fan table.

What temperature difference should I enter?

Use the supply-to-room difference, not the thermostat setting. Cooling designs are often near 18°F to 20°F. Heat-pump heating rises are often smaller. Gas furnace rises are larger and are printed as an allowable range on the furnace. Stay inside the range the equipment is built for.

Where does the 1.08 factor come from?

It is 60 minutes per hour times the density of standard air, about 0.075 lb/ft³, times the specific heat of air, about 0.24 BTU/lb·°F. That product is about 1.08. It describes sea-level standard air and sensible heat only.

Will more airflow fix a hot room?

Only if the room is short on supply air and the duct can carry more without robbing other rooms. More CFM at the blower does not help a closed room with a tiny branch. Size the branch from the room’s CFM, and look for a closed damper, a disconnected run, or a missing return.

Does this include humidity?

The sensible equation moves temperature, not moisture. Latent load needs the moisture calculation from a full load procedure. If you put total BTU, sensible plus latent, into this equation, the CFM will be higher than the temperature difference alone would justify.